7 REMOTE OPERATION
7.3 Setting RUN-PAUSE Contacts
143
7
7.3 Setting RUN-PAUSE Contacts
RUN-PAUSE contacts can be set. RUN-PAUSE contacts are used to perform remote RUN or STOP, or remote PAUSE using
a contact.
[CPU Parameter] [Operation Related Setting] [RUN-PAUSE Contact Setting]
Window
Displayed items
When setting the PAUSE contact, be sure to also set the RUN contact. (The PAUSE contact cannot be set
alone.)
7.4 Remote RESET
This function externally resets a CPU module in the STOP state (including that stopped due to an error). Even when the RUN/
STOP/RESET switch of a CPU module is set to RUN, the CPU module can be reset in the STOP state.
Enabling remote RESET
Performing remote RESET requires setting for enabling remote reset.
[CPU Parameter] [Operation Related Setting] [Remote Reset Setting]
Window
Displayed items
Executing method
Using an engineering tool
Perform remote RESET with the remote operation of the engineering tool. ( GX Works3 Operating Manual)
By an external device using SLMP
Perform remote RESET with the SLMP command. ( SLMP Reference Manual)
Item Description Setting range Default
RUN Set the contact that controls RUN for the CPU module. R00CPU, R01CPU, and R02CPU: X0 to X1FFF
Other CPU modules: X0 to X2FFF
PAUSE Set the contact that controls PAUSE for the CPU module. R00CPU, R01CPU, and R02CPU: X0 to X1FFF
Other CPU modules: X0 to X2FFF
Item Description Setting range Default
Remote RESET Set whether or not to enable the remote RESET. Disable
Enable
Disable