88
2 CPU MODULE OPERATION PROCESSING
2.2 Operation Processing When Operating Status Is Changed
2.2 Operation Processing When Operating Status Is
Changed
This displays operation processing when the operating status of the CPU module is changed.
*1 For details on the initial label value setting for the Process CPU and SIL2 Process CPU, refer to the following.
Page 322 LABEL INITIALIZATION FUNCTION
CPU module
operating
status
CPU module processing
Program External output Device memory
Other than Y Y
STOP RUN Executes the program from the
start.
Determines the status
depending on the setting of
"Output Mode Setting at STOP
to RUN" in the CPU parameter.
( Page 89 Output mode at
operating status change (STOP
to RUN))
Retains the device memory
status immediately before the
RUN state. However, if a device/
label initial value has been set,
this initial value is set.
*1
Clears
local devices.
Determines the status
depending on the setting of
"Output Mode Setting at STOP
to RUN" in the CPU parameter.
( Page 89 Output mode at
operating status change (STOP
to RUN))
RUN STOP Executes the program up to the
END instruction and then stops.
Saves the output (Y) status
immediately before the STOP
state, and all points turn off.
Retains the device memory
status immediately before the
STOP state.
Saves the output (Y) status
immediately before the STOP
state, and all points turn off.
RUN PAUSE Stops the operation after the
execution of one scan.
Retains the output (Y) status
immediately before the PAUSE
state.
Retains the device memory
status immediately before the
PAUSE state.
Retains the output (Y) status
immediately before the PAUSE
state.
PAUSE RUN Executes the program from the
start.
Retains the output (Y) status
immediately before the RUN
state.
Retains the device memory
status immediately before the
RUN state. Clears local devices.
Retains the output (Y) status
immediately before the RUN
state.
PAUSE STOP Operation remains stopped. Saves the output (Y) status
immediately before the STOP
state, and all points turn off.
Retains the device memory
status immediately before the
STOP state.
Saves the output (Y) status
immediately before the STOP
state, and all points turn off.
STOP PAUSE Operation remains stopped. Retains the output (Y) status
immediately before the PAUSE
state.
Retains the device memory
status immediately before the
PAUSE state.
Retains the output (Y) status
immediately before the PAUSE
state.

Table of Contents