37 FUNCTIONS
37.2 Tracking Transfer
631
37
■Global device setting
Set devices and their ranges for each tracking block No.
[CPU Parameter] [Redundant System Settings] [Tracking Setting] [Device/Label Detailed Setting] [Global
Device Setting]
To input devices and their ranges set in "Device/Label Memory Area Setting" in a batch, click the [Device
Setting Reflection] button.
Safety tracking transfer setting
Set tracking transfer of the information required for safety control.
[CPU Parameter] [Redundant System Settings] [Safety Tracking Setting]
Item Description
Device Setting Reflection Reflects the device setting of "Device/Label Memory Area Setting" in the CPU parameter.
(Except for the annunciator (F), link special relay (SB), and link special register (SW))
Tracking block No. Select the number of a tracking block to be set.
File Register Setting Enter a file name of the file register file.
This item is valid only when the file register (ZR) is selected in the device name field.
Device Select a device to be transferred. ( Page 624 Devices that can be specified)
Start/End Specify a range of devices to be transferred.
Item Description Setting range Default
Safety Control Data
Tracking Setting
Signal Flow Memory
(Safety) Tracking Setting
Set whether to transfer the data to be used for safety
control or not. "Signal Flow Memory (Safety) Tracking
Setting" and "Safety Device/Label, Standard/Safety Label
Tracking Setting" are set according to "Safety Control
Data Tracking Setting".
• Do Not Transfer
• Transfer
Transfer
Safety Device/Label,
Standard/Safety Label
Tracking Setting