538
33 FUNCTIONS
33.1 Safety Operation Mode
Switching the safety operation mode
This section describes how to switch the safety operation mode.
Safety operation mode transition timing
The timing at which safety operation mode switches is shown below.
The Safety CPU retains the safety operation mode status even when the power is turned off, or a reset is
performed.
Safety operation mode switching direction Safety operation mode switch timing
TEST MODE SAFETY MODE When the CPU module is powered off and on or is reset after the safety
operation mode switching operation
SAFETY MODE TEST MODE At the safety operation mode switching operation
(1) After switching from TEST MODE to SAFETY MODE, the safety operation
mode will be SAFETY MODE (wait-for-restart). (The status will be wait-for-
restart until the CPU module is powered off or is reset.) An error occur if the
Safety CPU is switched to RUN status when in SAFETY MODE (wait-for-
restart).
(2) After switching the safety operation mode (TEST MODE SAFETY
MODE), the mode will switch to SAFETY MODE when the CPU module is
powered off and on or is reset.
(3) After switching the safety operation mode (SAFETY MODE TEST
MODE), the mode will switch to TEST MODE.
(1)
(2)
(3)
Safety operation mode
The CPU module is
powered off or being
reset.
TEST MODE
SAFETY MODE
(wait-for-restart)
The CPU module is
powered off or being
reset.
SAFETY MODE
TEST MODE
User operation
Power-on/Reset of the CPU
module
Writing programs and parameters
to the CPU module
Mode switching (other than RUN)
(TEST MODE → SAFETY MODE)
Power-off/Reset of the CPU
module
Power-on/Reset of the CPU
module
Mode switching
(SAFETY MODE → TEST MODE)
Factory default