36 PROCEDURE FOR STARTING UP A SYSTEM USING THE SIL2 PROCESS CPU
36.6 Writing Data to the Programmable Controller
603
36
36.6 Writing Data to the Programmable Controller
Write the set parameters and created programs to the CPU module.
[Online] [Write to PLC]
Operating procedure
*1 When one of both systems is started up first, the window asking for writing the data to only the connected system appears.
To operate CPU modules, write system parameters, CPU parameters (standard/safety), and program files
(standard/safety). To operate I/O modules and intelligent function modules, write module parameters or
module extension parameters.
When new parameters have been set or the set parameters have been changed, reset the CPU module.
( MELSEC iQ-R CPU Module User's Manual (Startup))
Use the [Select Favorites] button to register frequently used items such as system parameters, CPU
parameters, and programs. Select [Setting] [Register Favorites Selection] from the menu on the "Online
Data Operation" window and set the items for the [Select Favorites] button.
1. Select system parameters, CPU parameters (standard/
safety), module parameters, and program files
(standard/safety) on the "Online Data Operation"
window. When FBs are used, select the corresponding
FB/FUN files (standard/safety).
2. Click the [Execute] button.
3. Click the [Yes] button.
*1
4. When writing the data to the programmable controller is
completed, click the [Close] button.