EasyManua.ls Logo

Mitsubishi Electric MELSEC iQ-R-R6SFM - Scan Configuration

Mitsubishi Electric MELSEC iQ-R-R6SFM
1028 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
568
35 BASIC CONCEPT
35.7 Scan Configuration
35.7 Scan Configuration
This section describes scan configurations of the CPU modules in a system using the SIL2 Process CPU.
Tracking transfer is performed during the END processing. ( Page 622 Tracking Transfer)
For details on the scan configuration other than tracking transfer, refer to Chapter 1. ( Page 38 Scan Configuration)
The following figure shows scan configurations of when both systems are started up simultaneously.
Both systems perform different processing.
: Performed, : Not performed
*1 Only the input refresh is performed. Whether or not to perform the output refresh depends on "Standby System Output Setting" of "CPU
Parameter". ( Page 652 Redundant System Operation Setting)
*2 The program operation is not performed with the default setting. Programs are executed according to "Both Systems Program
Executions Setting" in "Program Setting" of "CPU Parameter". ( Page 647 Program Execution in Both Systems)
Processing Control system Standby system
Initial processing/initial processing (when switched to RUN) 
I/O refresh 
*1
Program operation 
*2
Tracking transfer 
END processing 
Program operation
Tracking transfer
CPU module is
switched to RUN
Initial processing
(when switched to RUN)
I/O refresh
Scan
time
END processing
Tracking transfer
CPU module is
switched to RUN
Initial processing
(when switched to RUN)
I/O refresh
Scan
time
END processing
Sending tracking data
Reception completion of
tracking data
<Control system> <Standby system>
Operation of the program
executed in both systems

Table of Contents

Related product manuals