48
1 RUNNING A PROGRAM
1.3 Data Communication and I/O Processing
Refresh mode
The CPU module performs I/O processing collectively at a specified timing.
The timing of the input refresh and output refresh follows the specified refresh timing setting.
Outline of the processing
The following describes the details of the refresh mode.
*1 The remote input refresh area indicates the area to be used when refresh is set to the input (X) in CC-Link IE Controller Network, CC-
Link IE Field Network, CC-Link IE Field Network Basic, MELSECNET/H, or CC-Link.
*2 Data in the engineering tool input area can be turned on or off by the following:
Test operation of an engineering tool
Writing data from the network module
Writing data from an external device using SLMP
*3 Data in the output (Y) device memory can be turned on or off by the following:
Test operation of an engineering tool
Writing data from the network module
Writing data from an external device using SLMP
Item Description
Input refresh At a specified timing (at END instruction execution or before specified program execution), input data are collectively
read out from the input modules (1), the OR processing with the engineering tool input area and remote input refresh
area is executed, and then the data are stored in the input (X) device memory.
Output refresh At a specified timing (at END instruction execution or before specified program execution), data in the output (Y)
device memory (2) are collectively output to the output module.
X0
Y22
(3)
(4)
(5)
(1)
(2)
Y20
*3
CPU module
CPU (operation
processing area)
Input (X) device memory
Input module access area
Output (Y) device memory
Input refresh
Network module
Network module
Input module
Output module
Output refresh
Remote input
refresh area
*1
Remote input
area for CC-Link
IE Field Network
Basic
Engineering tool input
area
*2
Remote output area for
CC-Link IE Field Network
Basic