Appendix 4 List of Special Relay Areas
SFC information
The following is a list of special relay areas relating to SFC information.
No. Name Data stored Details Set by (setting timing) CPU
SM320 Presence/absence of SFC
program
Off: No SFC program
On: SFC program
This relay switches to on if an SFC
program has been registered, and
switches to off if it has not.
S (Initial) Rn
*1
RnP
*1
SM321 Start/stop SFC program Off: SFC program not
executed (stop)
On: SFC program
executed (start)
The same value as SM320 is set for the
default value. (This relay automatically
turns on if there is an SFC program.)
SFC program execution is stopped if this
relay switches from on to off, and
execution is restarted when it switches
from off to on.
If this relay switches off before SFC
program processing, execution of the
SFC program is not started.
S (Initial)/U Rn
*1
RnP
*1
SM322 SFC program start status Off: Initial start
On: Resumption
If the SFC program start mode in the
parameters is off for initial start, off is set
for the default, and if resumption, on is
set.
S (Initial)/U Rn
*1
RnP
*1
SM323 Presence/absence of
continuous transition for
entire block
Off: No continuous
transition
On: Continuous transition
Sets whether there is a continuous
transition for blocks for which no SFC
information device continuous transition
bit has been set.
No continuous transition when off.
Continuous transition when on.
There is no effect on operation for blocks
for which the continuous transition bit has
been set.
URn
*1
RnP
*1
SM324 Continuous transition
prevention flag
Off: When transition
executed
On: When there is no
transition
This relay switches to off during operation
in modes with continuous transition, or
during continuous transition, and switches
to on when it is not a continuous
transition.
The relay is always on during operation in
modes with no continuous transition.
S (Status change) Rn
*1
RnP
*1
SM325 Output mode at block stop Off: Off
On: Hold
Selects whether to retain coil output for
active steps during block stoppages.
The default value when the output mode
for block stoppages in the parameters is
coil output off is off, and on when coil
output is retained.
All coil outputs are turned off when off.
Coil outputs are retained when on.
S (Initial)/U Rn
*1
RnP
*1
SM326 SFC device/label clear
mode
Off: Device/label clear
On: Device/label retain
Select the device status (all devices and
labels (including latch labels) excluding
step relay (S)) when the CPU module
status changes from STOP program
write RUN.
This relay is valid only when an SFC
program exists after program writing.
This relay is valid not only when an SFC
program is written, but also when the
program file and the parameter file are
written.
When the Process CPU is used, only
labels are cleared at the program writing
to the programmable controller after data
are rebuilt even though this relay is on.
URn
*1
RnP
*1