5 - 135
Chapter 5 Data Used for Positioning Control
Setting value
Default
value
Buffer memory address
Set with a decimal.
Setting
value
Positioning data No.
1 to 600
7000 to7004
9001
9002
9003
9004
K
: Positioning data No.
: Block start designation
: Machine HPR
: Fast-HPR
: Current value changing
: Simultaneous starting of multiple axes
0 4300+100n
Set with a decimal.
Setting
value
K
Positioning starting point No.
The Simple Motion module resets the value to "0" automatically when the
continuous operation is interrupted.
1 to 50
0 4301+100n
Set with a decimal.
K
1
Error reset request
Setting value
The Simple Motion module resets the value to "0" automatically after the axis
error reset is completed.
Indicates that the axis error reset is completed.
1: Axis error is reset.
0 4302+100n
Set with a decimal.
K
1
Restart command
Setting value
The Simple Motion module resets the value to "0" automatically after restart
acceptance is completed. (Indicates that the restart acceptance is completed.)
1: Restarts
0 4303+100n
n: Axis No.-1