13 - 104 
Chapter 13  Control Sub Functions 
 
13.7.11 Operation setting for incompletion of HPR function 
The "Operation setting for incompletion of HPR function" is provided to select whether 
positioning control is operated or not, when HPR request flag is ON. 
 
This section explains the "Operation setting for incompletion of HPR function" as 
follows: 
 [1] Control details 
  [2] Precautions during control 
  [3] Setting method of "Operation setting for incompletion of HPR function" 
 
[1]  Control details 
 
When "[Pr.55] Operation setting for incompletion of HPR" is valid, this function 
related to the command speed, monitor data, speed limit value, is shown below. 
 
Item 
[Pr.55] Operation setting for incompletion of HPR 
"0: Positioning control is not 
executed." and   
"HPR request flag ON" 
"1: Positioning control is 
executed." and   
"HPR request flag ON" 
 
  Machine HPR 
 
  JOG operation 
 
  Inching operation 
 
  Manual pulse generator operation 
 
  Current value changing using current 
value changing start No. (No. 9003). 
*1
 
*1
 
The positioning control is impossible to 
start/restart in the following case. 
 
  1-axis linear control 
 
  2/3/4-axis linear interpolation control 
 
  1/2/3/4-axis fixed-feed control 
 
  2-axis circular interpolation control 
with sub point designation 
 
  2-axis circular interpolation control 
with center point designation 
 
  1/2/3/4-axis speed control 
 
 Speed-position switching control  
(INC mode/ ABS mode)   
 
  Position-speed switching control 
 
  Current value changing using 
positioning data No. (No.1 to 600). 
 
*1
 
Control mode switching 
 
*1
 
: Positioning start possible (Execution possible) 
: Positioning start impossible (Execution not possible) 
1: There may be restrictions in the operation for incompletion of HPR depending on the setting or 
specifications of the servo amplifier. Refer to the servo amplifier instruction manual for details. 
 
[2]  Precautions during control 
 
(1) The error "Start at HPR incomplete" (error code: 547) occurs if HPR request 
flag ([Md.31] Status: b3) is executed the positioning control by turning on, 
when "0: Positioning control is not executed" is selected the operation setting 
for incompletion of HPR setting, and positioning control will not be performed. 
At this time, operation with the manual control (JOG operation, inching 
operation, manual pulse generator operation) is available.