3 - 16
Chapter 3 Specifications and Functions
Device
No.
Signal name Details
X10
X11
X12
X13
X14
X15
X16
X17
X18
X19
X1A
X1B
X1C
X1D
X1E
X1F
Axis 1
Axis 2
Axis 3
Axis 4
Axis 5
Axis 6
Axis 7
Axis 8
Axis 9
Axis 10
Axis 11
Axis 12
Axis 13
Axis 14
Axis 15
Axis 16
BUSY
(Note-1)
OFF: Not BUSY
ON: BUSY
This signal turns ON at the start of positioning, HPR or JOG operation. It turns OFF
when the "[Da.9] Dwell time/JUMP destination positioning data No." has passed after
positioning stops. (This signal remains ON during positioning.)
This signal turns OFF when the positioning is stopped with step operation.
During manual pulse generator operation, this signal turns ON while the "[Cd.21]
Manual pulse generator enable flag" is ON.
This signal turns OFF at error completion or positioning stop.
Important
(Note-1): The BUSY signal turns ON even when position control of movement amount 0 is
executed. However, since the ON time is short, the ON status may not to be detected
in the sequence program.