● If the digital operation value exceeds the range of -32768 to 32767 as a result of shift addition, the digital operation value
is fixed to the lower limit value (-32768) or the upper limit value (32767).
● For the extension A/D converter module, go to "Ext. module 1_Module parameter" and set "Ext. module 1_CH A/D
conversion enable/disable setting" to "0: Enable", and then set the value to be added in CH Shifting amount to
conversion value (RWw12 to RWw15).
(3) Setting example
For the channel with the set input range of -10 to 10V, of the main A/D converter module, settings are
made as follows:
•CH Shifting amount to conversion value (RWw2 to RWw5): 20000
The digital output values and digital operation values are as follows:
*1 Because the value exceeds the range of -32768 to 32767, it is fixed to 32767 (the upper limit value).
Input voltage (V) Digital output value Digital operation value
-10 -16000 4000
-5 -8000 12000
0 0 20000
5 8000 28000
10 16000
32767
*1
1) Digital output value
(before adjustment)
Analog input voltage (V)
2) Digital operation value
(after adjustment)
Shifting amount to
conversion value
2) Digital operation value
1) Digital output value
+20000
+
16000
4000
32767
36000
0
-16000
100-10