114
If the digital operation value exceeds the range of -32768 to 32767 as a result of shift addition, the digital operation value
is fixed to the lower limit value (-32768) or the upper limit value (32767).
For the extension A/D converter module, go to "Ext. module 1_Module parameter" and set "Ext. module 1_CH A/D
conversion enable/disable setting" to "0: Enable", and then set the value to be added in CH Shifting amount to
conversion value (RWw12 to RWw15).
(3) Setting example
Ex.
For the channel with the set input range of -10 to 10V, of the main A/D converter module, settings are
made as follows:
•CH Shifting amount to conversion value (RWw2 to RWw5): 20000
The digital output values and digital operation values are as follows:
*1 Because the value exceeds the range of -32768 to 32767, it is fixed to 32767 (the upper limit value).
Input voltage (V) Digital output value Digital operation value
-10 -16000 4000
-5 -8000 12000
0 0 20000
5 8000 28000
10 16000
32767
*1
1) Digital output value
(before adjustment)
Analog input voltage (V)
2) Digital operation value
(after adjustment)
Shifting amount to
conversion value
2) Digital operation value
1) Digital output value
+20000
+
16000
4000
32767
36000
0
-16000
100-10