132
(7) Input interval and ON and OFF time of Trigger conversion request
When turning on Trigger conversion request from off, the ON/OFF operation of Trigger conversion request should
satisfy the reference values of the following items:
Input interval of Trigger conversion request
ON time of Trigger conversion request
OFF time of Trigger conversion request
(a) When Trigger conversion request (RY19) of the main A/D converter module is
assigned to Remote input (RX) using the external signal assignment function
The following table lists the input interval, ON time, and OFF time of Remote input (RX) to which Trigger
conversion request (RY19) is assigned.
*1 The response time of the extension input module is the minimum time period from an input of the extension input module
until the notification of the input to the main A/D conversion module. This time is given by the following:
(Input response time setting) + 0.5 [ms]
Item Reference value
Input interval of the trigger conversion request
(Response time of the extension input module)
*1
[ms] or longer
ON time of the trigger conversion request
OFF time of the trigger conversion request