200
(5) Trigger conversion completed clear request
• Changing Trigger conversion completed clear request (RY1A, RY2A) from No request (OFF) to Clear
request (ON) during Conversion completed (ON) of Trigger conversion completed flag (RX19, RX29) results
in Trigger conversion completed flag (RX19, RX29) turning from Conversion completed (ON) to Waiting for
conversion (OFF).
• Changing Trigger conversion completed clear request (RX19, RX29) from No request (OFF) to Clear
request (ON) during Waiting for conversion (OFF) of Trigger conversion completed flag (RX19, RX29) does
not affect Trigger conversion completed flag (RX19, RX29), which remains Waiting for conversion (OFF).
• Even after Trigger conversion completed flag (RX19, RX29) turns to Conversion completed (ON), Trigger
conversion completed flag (RX19, RX29) remains Conversion completed (ON) unless Trigger conversion
completed clear request (RY1A, RY2A) is turned from No request (OFF) to Clear request (ON).
For the timing "OFF→ON→OFF", refer to the following:
• Trigger conversion completed flag ( Page 194, Appendix 1.1 (8))
For the trigger conversion function, refer to the following:
• Trigger Conversion Function ( Page 127, Section 8.15)
(a) Device number
The device numbers of this output signal are as follows:
(6) Maximum value/minimum value reset request
Turning on and off Maximum value/minimum value reset request (RY1D, RY2D) allows CH Maximum value
(address: 0601H, 0603H, 0605H, 0607H, 0701H, 0703H, 0705H, 0707H) and CH Minimum value (address:
0602H, 0604H, 0606H, 0608H, 0702H, 0704H, 0706H, 0708H) to be cleared.
For the timing "OFF→ON→OFF", refer to the following:
• Maximum value/minimum value reset completed flag ( Page 196, Appendix 1.1 (10))
(a) Device number
The device numbers of this output signal are as follows:
(7) External power supply monitor request flag
Turn on this signal to activate the external power supply monitoring function.
For the timing "OFF→ON→OFF", refer to the following:
External power supply monitor state flag ( Page 196, Appendix 1.1 (11))
(a) Device number
The device number of this output signal is as follows:
Signal name Main A/D converter module Extension A/D converter module
Trigger conversion completed clear request RY1A RY2A
Signal name Main A/D converter module Extension A/D converter module
Maximum value/minimum value reset request RY1D RY2D
Signal name Main A/D converter module Extension A/D converter module
External power supply monitor request flag RY1F