215
APPX
A
Appendix 3 Details of Remote Buffer Memory
(13)Averaging process specification
This area is used for setting sampling processing or selecting the type of averaging processing for each channel.
There are the following types of averaging processing: time average, count average, and moving average.
(a) Enabling the setting
Turn on and off Initial data setting request flag (RY9) to enable the setting.
(b) Default value
The default value is Sampling processing (0H) for all channels.
(c) Remote buffer memory address
The remote buffer memory addresses of this area are as follows:
In the trigger conversion mode or synchronous communication mode, the setting of Averaging process setting (address:
0104H and 0204H) is ignored and the sampling processing is performed.
A channel to which a value out of the above range is written operates with the sampling processing.
Processing method Setting value
Sampling processing 0H
Time average 1H
Count average 2H
Moving average 3H
Remote buffer memory name
Main A/D converter module Extension A/D converter module
CH1 CH2 CH3 CH4 CH1 CH2 CH3 CH4
Averaging process specification 0104H 0204H
b15 to b12 b11 to b8 b7 to b0tob3b4
CH1CH2CH3CH4

Table of Contents