Appendix 3 Details of Remote Buffer Memory
(26)Parameter area initialization command
This command is used to set parameters in remote buffer memory areas and non-volatile memory to a default
value.
In the event of a non-volatile memory data error (parameter) (error code: 0130H), using this command makes it
possible to recover the module.
(a) Behavior of parameter area initialization
Setting Parameter area initialization command (address:1002H) to Commanded (1) sets the parameters in the
non-volatile memory back to default values.
(b) Default value
The default value is Not commanded (0).
(c) Remote buffer memory address
The remote buffer memory address of this area is as follows:
An execution of Parameter area initialization command (address: 1002H) does not clear the following remote input signals
and remote registers:
• Warning flag (RX7)
• Error flag (RXA)
• Alert output signal (RX18, RX28)
• Input signal error detection signal (RX1C, RX2C)
In addition, Remote READY (RXB) does not turn on.
After the execution of Parameter area initialization command (address: 1002H), turning off and on the module power supply
enables the module to operate normally.
Remote buffer memory name Main A/D converter module Extension A/D converter module
Parameter area initialization command 1002H
The values of b1 to b15 are fixed to 0.
b0b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1
0000000000 0000 0
0: Not commanded
1: Commanded
Controlled by the A/D converter module
Parameters of non-volatile memory
Parameter area initialization command
(address: 1002H)
Parameter area initialization completed
(address: 1003H)
Controlled by the program
Set parameters Default values
Not
commanded (0)
Not
commanded (0)
Commanded (1)
Not
performed (0)
Not performed (0)
Completed
(1)