40
*1 This value is the value of factory default or the value of initialization by Parameter area initialization command (address:
1002H).
*2 This shows whether reading/writing data from/to a program is possible.
R: Readable
W: Writable
*3 This shows the items enabled by turning on and off Initial data setting request flag (RY9).
Main module
Module-based
parameter data
256, 257 0100H, 0101H System area
258 0102H A/D conversion enable/disable setting 0000H R/W
259 0103H Range setting 0000H R/W
260 0104H Averaging process setting 0000H R/W
261 0105H
CH1 Time average/Count average/Moving
average
0R/W
262 0106H
CH2 Time average/Count average/Moving
average
0R/W
263 0107H
CH3 Time average/Count average/Moving
average
0R/W
264 0108H
CH4 Time average/Count average/Moving
average
0R/W
265 0109H Input signal error detection setting 0000H R/W
266 to 269 010AH to 010DH System area
270 010EH Alert output setting 000FH R/W
271 010FH CH1 Process alarm lower lower limit value 0 R/W
272 0110H CH1 Process alarm lower upper limit value 0 R/W
273 0111H CH1 Process alarm upper lower limit value 0 R/W
274 0112H CH1 Process alarm upper upper limit value 0 R/W
275 0113H CH2 Process alarm lower lower limit value 0 R/W
276 0114H CH2 Process alarm lower upper limit value 0 R/W
277 0115H CH2 Process alarm upper lower limit value 0 R/W
278 0116H CH2 Process alarm upper upper limit value 0 R/W
279 0117H CH3 Process alarm lower lower limit value 0 R/W
280 0118H CH3 Process alarm lower upper limit value 0 R/W
281 0119H CH3 Process alarm upper lower limit value 0 R/W
282 011AH CH3 Process alarm upper upper limit value 0 R/W
283 011BH CH4 Process alarm lower lower limit value 0 R/W
284 011CH CH4 Process alarm lower upper limit value 0 R/W
285 011DH CH4 Process alarm upper lower limit value 0 R/W
286 011EH CH4 Process alarm upper upper limit value 0 R/W
287 011FH Digital clipping enable/disable setting 000FH R/W
288 0120H Scaling enable/disable setting 000FH R/W
289 0121H CH1 Scaling lower limit value 0 R/W
290 0122H CH1 Scaling upper limit value 0 R/W
291 0123H CH2 Scaling lower limit value 0 R/W
292 0124H CH2 Scaling upper limit value 0 R/W
293 0125H CH3 Scaling lower limit value 0 R/W
294 0126H CH3 Scaling upper limit value 0 R/W
295 0127H CH4 Scaling lower limit value 0 R/W
296 0128H CH4 Scaling upper limit value 0 R/W
297 to 511 0129H to 01FFH System area
Extension module 1
Module-based
parameter data
512 to 767 0200H to 02FFH
The remote buffer memory areas of the
connected extension module are assigned.
768 to 1279 0300H to 04FFH System area
Type
Address
Description
Default
value
*1
Read/Write
*2
Necessity
of RY9
*3
Decimal Hexadecimal