40
*1 This value is the value of factory default or the value of initialization by Parameter area initialization command (address:
1002H).
*2 This shows whether reading/writing data from/to a program is possible.
R: Readable
W: Writable
*3 This shows the items enabled by turning on and off Initial data setting request flag (RY9).
Main module
Module-based
parameter data
256, 257 0100H, 0101H System area 
258 0102H A/D conversion enable/disable setting 0000H R/W
259 0103H Range setting 0000H R/W
260 0104H Averaging process setting 0000H R/W
261 0105H
CH1 Time average/Count average/Moving
average
0R/W
262 0106H
CH2 Time average/Count average/Moving
average
0R/W
263 0107H
CH3 Time average/Count average/Moving
average
0R/W
264 0108H
CH4 Time average/Count average/Moving
average
0R/W
265 0109H Input signal error detection setting 0000H R/W
266 to 269 010AH to 010DH System area 
270 010EH Alert output setting 000FH R/W
271 010FH CH1 Process alarm lower lower limit value 0 R/W
272 0110H CH1 Process alarm lower upper limit value 0 R/W
273 0111H CH1 Process alarm upper lower limit value 0 R/W
274 0112H CH1 Process alarm upper upper limit value 0 R/W
275 0113H CH2 Process alarm lower lower limit value 0 R/W
276 0114H CH2 Process alarm lower upper limit value 0 R/W
277 0115H CH2 Process alarm upper lower limit value 0 R/W
278 0116H CH2 Process alarm upper upper limit value 0 R/W
279 0117H CH3 Process alarm lower lower limit value 0 R/W
280 0118H CH3 Process alarm lower upper limit value 0 R/W
281 0119H CH3 Process alarm upper lower limit value 0 R/W
282 011AH CH3 Process alarm upper upper limit value 0 R/W
283 011BH CH4 Process alarm lower lower limit value 0 R/W
284 011CH CH4 Process alarm lower upper limit value 0 R/W
285 011DH CH4 Process alarm upper lower limit value 0 R/W
286 011EH CH4 Process alarm upper upper limit value 0 R/W
287 011FH Digital clipping enable/disable setting 000FH R/W
288 0120H Scaling enable/disable setting 000FH R/W
289 0121H CH1 Scaling lower limit value 0 R/W
290 0122H CH1 Scaling upper limit value 0 R/W
291 0123H CH2 Scaling lower limit value 0 R/W
292 0124H CH2 Scaling upper limit value 0 R/W
293 0125H CH3 Scaling lower limit value 0 R/W
294 0126H CH3 Scaling upper limit value 0 R/W
295 0127H CH4 Scaling lower limit value 0 R/W
296 0128H CH4 Scaling upper limit value 0 R/W
297 to 511 0129H to 01FFH System area 
Extension module 1
Module-based
parameter data
512 to 767 0200H to 02FFH
The remote buffer memory areas of the
connected extension module are assigned.

768 to 1279 0300H to 04FFH System area 
Type
Address
Description
Default
value
*1
Read/Write
*2
Necessity
of RY9
*3
Decimal Hexadecimal