3  SPECIFICATIONS
3.2  Performance Specifications
25
3
NZ2MF2S1-32D DC input module
*1 If the input response time is set to "0ms", the actual input response time is 80s at OFF  ON, and 160s at ON  OFF.
*2 It is the noise immunity of when the input response time setting value is other than "0ms". Note that the module is easily affected by 
noise if "0ms" is set.
*3 Only one wire can be connected to a terminal of the terminal block for module power supply and FG or the terminal block for input. 
Multiple wires cannot be connected to a terminal. Connecting two or more wires may cause a poor contact.
*4 It is recommended to use the bar solderless terminal for wiring.
Item NZ2MF2S1-32D
Station type Slave station
Number of input points 32 points
Rated input voltage 24VDC (ripple rate: 5% or less) (Allowable voltage range: 20.4 to 28.8VDC)
Rated input current 6.0mA TYP. (for 24VDC)
Isolation method Photocoupler isolation
Max. number of simultaneous input points 100%
ON voltage/ON current 15VDC or more/4mA or more
OFF voltage/OFF current 5VDC or less/1.7mA or less
Input resistance 3.8k
Input response time OFFON 0ms
*1
/0.2ms/1ms/1.5ms/5ms/10ms/20ms/70ms
(Initial setting: 10ms)
ONOFF
Input type Positive common/negative common shared type
Withstand voltage 500VAC for 1 minute between all DC external terminals and the ground
Insulation resistance 10M or higher between all DC external terminals and ground (500VDC insulation resistance tester)
Noise immunity
*2
Noise voltage 500Vp-p, noise width 1s, noise frequency 25 to 60Hz (DC type noise simulator 
condition)
Protection degree IP2X
Wiring method for common 32 points/common (two points) (1-wire, spring clamp terminal block type)
External interface Communication part RJ45 connector
Module power supply part Terminal block for module power supply and FG (Two-piece spring clamp terminal block)
I/O part 34-point two-piece spring clamp terminal block
Applicable DIN rail TH35-7.5Fe, TH35-7.5Al (compliant with IEC 60715/JIS C 2812)
Applicable wire size For power supply Stranded wire: 0.3 to 1.5 (22 to 16 AWG), terminal slot size: 2.8mm  2.0mm
*4
For I/O Stranded wire: 0.3 to 1.5 (22 to 16 AWG), terminal slot size: 2.4mm  1.5mm
*4
Applicable solderless 
terminal
Terminal block for module 
power supply and FG
*3
Page 81 Applicable solderless terminal
Terminal block for input
*3
Page 85 Applicable solderless terminal
Number of occupied stations One station
Reference response time 1ms
Communication cable An Ethernet cable that meets the 100BASE-TX standard
For details, refer to the following.
 CC-Link IE Field Network Basic Reference Manual
Module power supply Voltage 24VDC (ripple rate: 5% or less) (Allowable voltage range: 20.4 to 28.8VDC)
Current 71mA or less (24VDC, all points ON)
Weight 0.25kg