5 - 22 5 - 22
MELSEC-Q
5 UTILITY PACKAGE (GX Configurator-AD)
Analog/digital conversion: Select a conversion type shown below for confirming
the correspondence between an analog value and a
digital value caused by the conversion characteristic.
Digital
analog
Analog
digital
Analog value: <When converted to a digital value>
Enter an analog value to be converted to a digital value
<When converted to an analog value>
The analog value converted from a digital value is displayed.
Digital value: <When converted to a digital value>
The digital value corresponding to an entered analog value is
displayed.
<When converted to an analog value>
Enter a digital value to be converted to an analog value.
POINT
The offset value is an analog input value (voltage or current) that will produce a
digital output value of 0.
The gain value is the analog value (voltage or current) output when the digital
input value set from the PLC CPU is as follows:
32000 (When Unipolar/Bipolar are selected)
(3) Explanation of screen command buttons
Range setting The entered offset/gain value is determined, and the I/O
characteristic diagram is updated.
Conversion
Conversion for the entered value is performed.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi GX Configurator-AD and is the answer not in the manual?

Mitsubishi GX Configurator-AD Specifications

General IconGeneral
BrandMitsubishi
ModelGX Configurator-AD
CategoryController
LanguageEnglish

Related product manuals