APP -4 APP -4
MELSEC-Q
A
PPENDI
X
Appendix 1.2 OGLOAD
Reads the offset/gain values of the user range setting of the A/D converter module to
the CPU.
Usable devices
Internal device
(System, user)
MELSECNET/H
Direct J \
Constant
Set data
Bit Word
File
register
Bit Word
Special
function
module
U
\G
Index
register
Z
K, H S
Other
(S) ———
(D) ———
Command
G.OGLOAD
Command
GP.OGLOAD
Un (S) (D)
Un (S) (D)
[Instruction
symbol]
[Execution
condition]
G.OGLOAD
GP.OGLOAD
Set data
Device Description Setting range Data type
Un Start I/O number of the module 0 to FEH Binary 16 bits
(S) Start number of the device in which control data is stored.
Within the range of the
specified device
Device name
(D)
Device that is turned ON 1 scan on completion of dedicated
instruction processing.
(D) + 1 also turns ON at an abnormal completion.
Within the range of the
specified device
Bit
Control data
1
of Q64AD-GH (1/2)
Device Item Set data Setting range Set by
(S) System area
(S) + 1 Completion status
Stores the status when the
instruction is complete.
0 : Normal completion
Other than 0: Abnormal completion
—System
(S) + 2 Pass data classification setting
Specify the voltage/current of the
offset/gain values to be read.
0: Voltage specified
1: Current specified
0 0 CH4 CH3 CH2 CH1
b15 b4b3b2b1b0
to
0000H to 000F H User
(S) + 3 System area
(S) + 4
(S) + 5
CH1 Industrial shipment settings offset value (L)
(H)
——System
(S) + 6
(S) + 7
CH1 Industrial shipment settings gain value (L)
(H)
——System
(S) + 8
(S) + 9
CH2 Industrial shipment settings offset value (L)
(H)
——System
(S) + 10
(S) + 11
CH2 Industrial shipment settings gain value (L)
(H)
——System
1 Set only the pass data classification setting (S)+2. If data is written to the area set by the system, the offset/gain values
will not be read properly.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi GX Configurator-AD and is the answer not in the manual?

Mitsubishi GX Configurator-AD Specifications

General IconGeneral
BrandMitsubishi
ModelGX Configurator-AD
CategoryController
LanguageEnglish

Related product manuals