5. PARAMETERS 
5 -  12 
 
5.2 Detailed list of parameters 
 
POINT 
 
Set a value to each "x" in the "Setting digit" columns. 
 
 
5.2.1 Basic setting parameters ([Pr. PA_ _ ]) 
Control 
mode 
No./symbol/ 
name 
Setting 
digit 
Function 
Initial 
value 
[unit] 
P S T 
PA01 
*STY 
Operation 
mode 
_ _ _ x  Control mode selection 
Select a control mode. 
0: Position control mode 
1: Position control mode and speed control mode 
2: Speed control mode 
3: Speed control mode and torque control mode 
4: Torque control mode 
5: Torque control mode and position control mode 
0h 
  _ _ x _  Operation mode selection 
0: Standard control mode 
1: Fully closed loop control mode 
4: Linear servo motor control mode 
6: DD motor control mode (except 400 V class servo amplifiers) 
Setting other than above will trigger [AL. 37 Parameter error]. The linear servo 
system, direct drive servo system and fully closed loop system are available for the 
MR-J4-_A_(-RJ) servo amplifiers of which software version is A5 or later. 
0h 
  _ x _ _  For manufacturer setting  0h       
  x _ _ _    1h