App. 4.8 Technical data 
App. 4.8.1 MR-J4 servo amplifier 
(1)  200 V class 
 
Item 
MR-J4-10_/MR-J4-20_/MR-J4-40_/ 
MR-J4-60_/MR-J4-70_/MR-J4W2-22B/ 
MR-J4W2-44B/MR-J4W2-77B/ 
MR-J4W3-222B/MR-J4W3-444B 
MR-J4-100_/MR-J4-200_/MR-J4-350_/ 
MR-J4-500_/MR-J4-700_/ 
MR-J4W2-1010B/MR-J4-11K_/ 
MR-J4-15K_/MR-J4-22K_ 
Main circuit (line voltage)
3-phase or 1-phase 200 V AC to 240 V AC, 
50 Hz/60 Hz 
3-phase 200 V AC to 240 V AC, 50 Hz/60 Hz 
Control circuit (line 
voltage) 
1-phase 200 V AC to 240 V AC, 50 Hz/60 Hz 
Power 
Interface (SELV) 
24 V DC, (required current capacity: MR-J4-_A, 500 mA; MR-J4-_B,  
300 mA; MR-J4W2-_B, 350 mA; MR-J4W3-_B, 450 mA) 
Control method  Sine-wave PWM control, current control method 
Functional safety (STO) 
IEC/EN 61800-5-2 
EN ISO 13849-1 category 3 PL d, IEC 61508 SIL 2, EN 62061 SIL CL 2, and EN 61800-5-2 SIL 2
Mean time to dangerous failure  MTTFd ≥ 100 [years] 
Effectiveness of fault monitoring of 
a system or subsystem 
DC = 90 [%] 
Average probability of dangerous 
failures per hour 
PFH = 1.68 × 10
-10
 [1/h] 
Mission time  TM = 20 [years] 
Response performance  8 ms or less (STO input off → energy shut off) 
Pollution degree  2 (IEC/EN 60664-1) 
Overvoltage category  III (IEC/EN 60664-1) 
Protection class  I (IEC/EN 61800-5-1) 
Short-circuit current rating (SCCR) 100 kA 
 
(2)  400 V class 
 
Item 
MR-J4-60_4/MR-J4-100_4/MR-J4-200_4/MR-J4-350_4/MR-J4-500_4/MR-J4-700_4/ 
MR-J4-11K_4/MR-J4-15K_4/MR-J4-22K_4 
Main circuit (line voltage) 3-phase 380 V AC to 480 V AC, 50 Hz/60 Hz 
Control circuit (line 
voltage) 
1-phase 380 V AC to 480 V AC, 50 Hz/60 Hz 
Power 
supply 
Interface (SELV)  24 V DC, (required current capacity: MR-J4-_A4, 500 mA; MR-J4-_B4, 300 mA) 
Control method  Sine-wave PWM control, current control method 
Safety function (STO) 
IEC/EN 61800-5-2 
EN ISO 13849-1 category 3 PL d, IEC 61508 SIL 2, EN 62061 SIL CL 2, and EN 61800-5-2 SIL 2
Mean time to dangerous failure  MTTFd ≥100 [years] 
Effectiveness of fault monitoring of 
a system or subsystem 
DC = 90 [%] 
Average probability of dangerous 
failures per hour 
PFH = 1.68 × 10
-10
 [1/h] 
Mission time  TM = 20 [years] 
Response performance  8 ms or less (STO input off → energy shut off) 
Pollution degree  2 (IEC/EN 60664-1) 
Overvoltage category  III (IEC/EN 60664-1) 
Protection class  I (IEC/EN 61800-5-1) 
Short-circuit current rating (SCCR) 100 kA