Motion 3000ES Escalator Control
36 Manual # 42-02-E001
F4-19 P37 Enable
Programmable error message:
1. Pit Flooded
2. Tandem Fault
3. Broken Belt
4. Brake Wear
5. Broken Step Chain
6. Brake Overheat
Not available on all software versions.
1-6 1 1
FUN5-Counters & Fault History
F5-01 Password setting Set passcode: default is 00000000.
F5-02 Usage time limit Limitation of the use time 0-9999hr 0
F5-03
Usage time bal-
ance
The rest of the use time 0-9999hr 0
F5-04 Clear fault log Clears the F6-01 fault history.
F5-05 Parameter Default
Resets all controller parameters to their
default values.
F5-06 Start counter Operational Counter 0-9999
F5-07
Construction
Mode
Construction Mode
0=OFF
1=ON
0
FUN6-Fault Display
F6-01 Fault display Fault display
FUN7- Software Ver. for EC-MCB
F7-01 Software version. Software version.
FUN8- Software Ver. for EC-SCB
F8-01 Software version Software version
Table 10. Controller Parameters
Param Name Description Value Default MCE