10 Maintenance, inspection and care
96 BA6820378-03 EN
Gree
n
LED
Yel-
low
LED
Red
LED
Humidity level Action
>20% R.H. Humidity increased, even though regener-
ation has been performed within the last 7
days.
The device may be inadequately dimen-
sioned or the silica gel may be contami-
nated.
Check the installation situation.
Are all transition points of the piping still
sealed tightly?
Contact MR Service & Complaint
[►Section 9, Page 83] if necessary.
>40% R.H. WARNING!
Humidity too high.
Regeneration imminent.
The device may be inadequately dimen-
sioned or the silica gel may be contami-
nated.
Check the installation situation.
Are all transition points of the piping still
sealed tightly?
Contact MR Service & Complaint
[►Section 9, Page 83] if necessary.
>40% R.H. WARNING!
Humidity is too high, even though regener-
ation has been performed within the last 7
days.
Check the installation situation.
Are all transition points of the piping still
sealed tightly?
Contact MR Service & Complaint
[►Section 9, Page 83] if necessary.
= LED OFF
= LED ON
= LED FLASHING