9 Troubleshooting
US SENTRY io 43
Condition Corrective Action
25 Relay contact not powered Most relays are dry—Check manual for wetting contact
26 View/export program logic
l
Check logic in cause & effect settings
l
Export logic in cause & effect settings
27 Cannot configure "two relay voting"
scheme
Create second voting scheme that uses same inputs with a
different output
28 Not all channels displayed on
dashboard
l
Change view configuration
l
Follow arrow to next screen showing additional channels
29 Fault code on screen Any fault code shown is derived from HART command 48. See
instrument display for more information
30 Can I export trends Copy file from SD card directory <dir>
31 Can I export cause & effect Copy file from SD card directory <dir>