SECTION 92: Menu Selecon
Table 9
Menu
Description
PARAMETER Sets the parameters for Swing door movement.
CONFIG Conguraon: Sets the parameters of the GT20 Control Features and Funcons.
DOUBLE DOOR Sets the Closing sequence and Interlock funcon.
DIAGNOSTICS Diagnosc Tools that display the status of various inputs.
ERROR ACTIVE X Displays Pending Acve Errors.
X Acve Error list is updated with the latest addions appearing at the end.
X A0 indicates the latest Acve error.
HISTORY ERROR X Displays all Acve Errors that were detected and then corrected or not corrected.
X H0 indicates the latest Acve error.
REINIT Reinializaon resets Sengs back to Factory Default
BLOCK? Locks/Unlocks Joysck
UPDATE SW Start the upgrade process from the USB Sck.
TEACH X Programs the Inial Setup, and nds Errors (if any).
X Programs a new Setup Procedure when deemed necessary.
Table 10
Element
Unit Type Default Value Description
Region BOTH EU Eu or US EU - Europe; US - United States
Soware version determined by UL Standards. Must be changed to US.
Vo Full Power 6 0..14 Opening speed (velocity open)
Low Energy 9 0...9
Vc Full Power 4 0..14 Closing speed (velocity closed)
Low Energy 9 0...9
TOEx Full Power 3s 0...60s TOEx sets the hold-open me resulng from acvaon signals from devices
connected to: terminals 9+10 for exterior acvaon and terminals 12+13 for
interior acvaon.
Low Energy 5s 3...60s
ANSI 156.19 for Low Energy:
TOEx must be no less than 5s.
TKey Full Power 5s 0...180s X TKey sets the hold-open me resulng from an acvaon signal from a device
(referred to as KEY) on terminals 2+3.
X With TOEx and TKey, you can set a dierent hold open mes for dierent
acvaon devices by using dierent terminals.
Low Energy 5s 3...180s
TPuGo Full Power 3s 0...180s Determines how long the Door Panel stays open.
Low Energy 3s 3...180s
TDelay Full & Low 0.2s 0.0...4.0s Tdelay sets the amount of me the door hesitates to allow the lock to release
before opening.
FDelay Full Power OFF OFF...7.0A Fdelay is a temporary “hold closed” force applied to the door to keep it closed
while the electric lock is being released. This parameter sets the amount of force
that is applied. FDelay is only acve if TDelay seng is greater than 0.
Low Energy OFF OFF...7.0A
TLock Full & Low 0.5s 0.0...4.0s Sets amount of me Door Panel will press against lock to engage it.
FLock Full & Low 2.0A OFF...7.0A Sets amount of force that is applied to the door to engage the lock at the closed
posion. It is only acve if TLock seng is greater than 0.
FSlam Full & Low OFF OFF...10 Accelerang funcon (force slam). For example: When a door panel needs to be
forced shut due to a latch or heavy seals.