EasyManua.ls Logo

Nachi FD - Page 14

Default Icon
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4.1 Setting procedure
4-2
INFO.
In EtherNet/IP, the device called a “slave” on DeviceNet is called an “adapter”.
("EtherNet/IP slave" in this controller means "EtherNet/IP adapter".)
In EtherNet/IP, the device called a “master” on DeviceNet is called an “scanner”.
("EtherNet/IP master" in this controller means "EtherNet/IP scanner".)
Setting example
The following figure shows the setting example of the configuration used in this chapter.
Configuration of Robot controller
Set master as module1 of base board. Set slave as module2 of base board.
Connect them to setting PC via a hub.
Fig. 4.1.2 Configuration example
Setting of field bus
CH1 AnyBusEtherNet/IP Mater module 1
CH2 No use
CH3 AnyBusEtherNet/IP Slave module 2
CH4 No use
Master detailed settings (CH1)
IP address and so on are omitted.
Input byte number 128
Output byte number 128
Slave detailed settings (CH3)
IP address and so on are omitted.
Input byte number 128
Output byte number 128
PC settings
The IP address of the PC must belong to the identical network with the robot controller.
Setting PC
HUB
Base board
Master Slave
Robot controller
172.18.233.71
172.18.233.59
172.18.233.60
RSLinx Classic
RSNetWorx for EtherNet/IP

Related product manuals