Wiring
FP0
7-13
Matsushita Automation Controls
7.6 Wiring the Terminal Type
7.6 Wiring the Terminal Type
A screw-down connection type terminal block socket for terminal of FP0 control unit and
analog I/ O unit is used. The terminal block socket and suitable wires are given below.
Terminal block socket
Suitable wire
Terminal block socket
Item Description
Manufacturer
Phoenix Contact Co.
Model
MC1,5/9-ST-3,5
Product number
1840434
Suitable wires (twisted wire)
Item Description
Control unit
Size: AWG #24 to 16
Conductor cross-sectional area: 0.3 to 1.25 mm
2
Analog I/O unit
Size: AWG #28 to 16
/
Conductor cross-sectional area: 0.08 to 1.25 mm
2
Pole terminal with a compatible insulation sleeve
If a pole terminal is being used, the following models are marketed by Phoenix Contact
Co.
Manufacturer Cross-sectional
area (mm
2
)
Size Product number
Phoenix Contact Co.
0.25 AWG #24 AI 0,25- 6YE
0.50 AWG #20 AI 0,5- 6WH
0.75 AWG #18 AI 0,75- 6GY
1.00 AWG #18
AI 1- 6RD
Pressure welding tool for pole terminals
Manufacturer
Phoenix Contact Co.
Type
CRIMPFOX UD6
Product number
12 04 43 6
When tightening the terminals of the terminal block socket, use a screwdriver (Phoenix
Contact Co., Product no. 1205037) with a blade size of 0.4 × 2.5. The tightening torque
should be 0.22 to 0.25 N
m (2.3 to 2.5 kgf
cm) or less.