Self-Diagnostic and Troubleshooting
FP0
10 - 15
Matsushita Automation Controls
10.3 Error Codes
10.3.3 Self-Diagnostic Error Codes
Error
code
Name of
error
Operation
status
Description and steps to take
E31 Interrupt
error 1
Stops An interrupt occurred without an interrupt request.
A hardware problem or error due to noise is possible.
Turn OFF the power and check the noise
conditions.
E32 Interrupt
error 2
Stops An interrupt occurred without an interrupt request.
A hardware problem or error due to noise is possible.
Turn OFF the power and check the noise
conditions.
There is no interrupt program for an interrupt which
occurred.
Check the number of the interrupt program and
change it to agree with the interrupt request.
E45 Operation
error
Selects Operation became impossible during a high-level
instruction. The cause of the operation error varies
depending on the instruction. In system register 26,
select “1: Continue operation” or “0: Stop”
E100
to
E199
Self-diagnos-
tic error set
by F148
Stops The error set using high-level instruction
F148(ERR)
has occurred.
Clear the error based on the set detection
E200
to
E299
(ERR)
instruction
Continues
conditions