Analog I/O Unit
FP0
4-19
Matsushita Automation Controls
4.7 Averaging Function
.
Note
In the read timing, the minimum and maximum values are
subtracted from the data from the last ten times, just as in
averaging processing of section 4.7.1, and the data from the
remaining eight times is used for the averaging.
ch1
ch0
ch1
Data from 8 times used for averaging
Check for disconnected wiring
70 msec70 msec
If a disconnected wire is detected, a value of K20000 is output.