Chapter 7 Calibration  55 
 
 
a.  With the laser output off, connect a calibrated ammeter to the 
PD Anode output of the driver and connect the circuit of Figure 
20 to the laser and PD outputs.  
 
If a calibrated ammeter (with 0.1 
µ
A resolution) is not available, 
place a calibrated DMM (with 0.1 mV resolution) to measure the 
voltage across the resistor, R3, as shown in Figure 20. Calculate 
the current in the following steps by using Ohm's Law: 
 
        I = V / R 
 
where V is the measured voltage across the resistor, and R is the 
measured load resistance. 
 
b.  With the unit in Im mode, press the 
LDD ON
 key to turn the 
laser output on. If a laser on delay has been set, wait that amount 
of time to allow the laser output to engage. 
 
c.  Start the calibration procedure by first pressing the 
MENU
 
button, then right arrow until the 
Calibration
 menu is reached, 
then presses the down arrow until the 
Im Calibration 
function 
is selected, then the right arrow key to execute the Im calibration 
function.  
 
d.  The output will be set at ½ full scale and allowed to settle. Once 
settled, enter the actual current measurement from the ammeter 
display, then select the 
Next
 soft button and press the right 
arrow. 
 
e.  The output will then be moved to ¼ the current set point and 
allowed to settle. Once settled, enter the actual current 
measurement from the ammeter display, then select the 
Next
 
soft button and press the right arrow. 
 
f.  The calibration procedure is complete. 
7.2.5  Remote Operation I
PD
 Current Calibration 
a.  With the laser output off, connect a calibrated ammeter to the 
photodiode anode output of the driver and connect the circuit of 
Figure 20 to the laser and photodiode outputs. 
 
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com