Menu 4.7 - holiday setting
To reduce energy consumption during a holiday you
can schedule a reduction in heating and hot water
temperature. Cooling, pool and solar panel cooling can
also be scheduled if the functions are connected.
If a room sensor is installed and activated the desired
room temperature (°C) is set during the time period.
This setting applies to all climate systems with room
sensors.
If a room sensor is not activated, the desired offset of
the heating curve is set. This setting applies to all cli-
mate systems without room sensors. One step is usually
enough to change the room temperature by one de-
gree, but in some cases several steps may be required.
Vacation scheduling starts at 00:00 on the start date
and stops at 23:59 on the stop date.
TIP
Complete holiday setting about a day before
your return so that roomtemperature and hot
water have time to regain usual levels.
TIP
Set the vacation setting in advance and activ-
ate just before departure in order to maintain
the comfort.
Menu 4.9 - advanced
Menu advanced has orange text and is intended for
the advanced user. This menu has several sub-menus.
Menu 4.9.1 - op. prioritisation
op. prioritisation
Setting range: 0 to 180 min
Default value: 30 min
Choose here how long the installation should work
with each requirement if there are several requirements
at the same time. If there is only one requirement the
installation only works with that requirement.
The indicator marks where in the cycle the installation
is.
If 0 minutes is selected it means that requirement is
not prioritised, but will only be activated when there
is no other requirement.
Menu 4.9.2 - auto mode setting
start cooling
Setting range: -20 – 40 °C
Default value: 25
stop heating
Setting range: -20 – 40 °C
Default values: 17
stop additional heat
Setting range: -25 – 40 °C
Default values: 5
filtering time
Setting range: 0 – 48 h
Default value: 24 h
When the operating mode is set to "auto", the indoor
module selects when start and stop of additional heat
and heat production is permitted, dependent on the
average outdoor temperature. If accessories for cooling
are present or if the heat pump has the integrated
cooling function and it is activated in the menu you
can also select the start temperature for cooling.
Select the average outdoor temperatures in this menu.
You can also set the time over which (filtering time)
the average temperature is calculated. If you select 0,
the present outdoor temperature is used.
Caution
It cannot be set "stop additional heat" higher
than "stop heating".
Caution
In systems where heating and cooling share
the same pipes "stop heating" cannot be set
higher than "start cooling".
Menu 4.9.3 - degree minute setting
current value
Setting range: -3000 – 3000
start compressor
Setting range: -1000 – -30
Default value: -60
start diff additional heat
Setting range: 100 – 1000
Default value: 700
diff. between additional steps
Setting range: 0 – 1000
Default value: 100
Degree minutes are a measurement of the current
heating requirement in the house and determine when
NIBE™ VVM 310Chapter 8 | Control - Menus48