English – 17
After the function test, check the fastening screws are positioned correctly.
The additional limit switches 5
P1
and 6
P1
(GREEN and WHITE, g. 21)
are potential-free switching contacts.
The CLOSING additional limit switch 1
E
(5
P1
and 6
P1
) is used as
a preliminary limit switch; therefore, it must be set to trigger when the door
reaches a distance of 5 cm from the ground.
The triggering of this limit switch prevents the execution of the “short reverse“
manoeuvre.
If the safety edge is triggered, it only performs the STOP. This limit switch must
always be connected to the control unit’s PRE-CLOSE input.
3.13 Changing direction of motor rotation
If the door moves in the opposite direction to the one desired during the position
learning phase, adjust:
•DIP switch 3 (TABLE 14A)
parameter P75 (TABLE 14B)
without having to set the positions again.
TABLE 14A
Phase
Operation to be performed
using
DIP switch 3
Graphical description
1 Set DIP switches 3 and 4 to ON
ON
1 2 3 4
OFF
ON
1 2 3 4
OFF
ON
1 2 3 4
OFF
ON
1 2 3 4
OFF
ON
1 2 3 4
OFF
ON
1 2 3 4
OFF
ON
1 2 3 4
OFF
2
The display shows two “Ls”
upside-down and back to back
3
Press and hold the rear button
located behind the board
/
4
Release the button when the
display shows the two “Ls”
inverted
5 Set all DIP switches to OFF
ON
1 2 3 4
OFF
ON
1 2 3 4
OFF
6
Set DIP switch 4 to ON to learn
the positions again
ON
1 2 3 4
OFF
ON
1 2 3 4
OFF
ON
1 2 3 4
OFF
ON
1 2 3 4
OFF
ON
1 2 3 4
OFF
ON
1 2 3 4
OFF
ON
1 2 3 4
OFF
TABLE 14B
Number
Operation to be performed
using
parameter P75
Graphical description
1 Set DIP switch 1 to ON
ON
1 2 3 4
OFF
ON
1 2 3 4
OFF
ON
1 2 3 4
OFF
ON
1 2 3 4
OFF
ON
1 2 3 4
OFF
ON
1 2 3 4
OFF
ON
1 2 3 4
OFF
2
Scroll to parameter P75 using
the rear buttons
/
3
Use the rear button to change
the value from "0" to "1"
/
4
Set all DIP switches to OFF to
exit the parameters menu
ON
1 2 3 4
OFF
ON
1 2 3 4
OFF
5
Set DIP switch 4 to ON to learn
the positions again
ON
1 2 3 4
OFF
ON
1 2 3 4
OFF
ON
1 2 3 4
OFF
ON
1 2 3 4
OFF
ON
1 2 3 4
OFF
ON
1 2 3 4
OFF
ON
1 2 3 4
OFF
3.14 Enabling partial opening
The control unit allows a partially open position to be set during the limit switch
setting.
If this position has not yet been set, the half-open option can be used without
having to learn the positions again (the door will open exactly halfway between
the upper and lower limit stops).
By default, the partially open (or half-open) position is deactivated and can be
enabled as follows:
TABLE 15 - Enabling partial opening
Number Operation to be performed Graphical description
1 Set DIP switch 1 to ON
ON
1 2 3 4
OFF
ON
1 2 3 4
OFF
ON
1 2 3 4
OFF
ON
1 2 3 4
OFF
ON
1 2 3 4
OFF
ON
1 2 3 4
OFF
ON
1 2 3 4
OFF
2
Use the rear buttons to scroll
to the parameter relating to the
input where you wish to connect
the NO contact for enabling
partial opening (e.g. UP input -
P100)
/
3 Set DIP switch 4 to ON
ON
1 2 3 4
OFF
ON
1 2 3 4
OFF
4
Use the rear buttons to set the
parameter value for the chosen
input to:
11 = it will only be possible to
perform partial opening and
not full opening.
12 = the next opening
command after the one given
for partial opening will open
the door fully.
5 Set all DIP switches to OFF
ON
1 2 3 4
OFF
ON
1 2 3 4
OFF
Enabling the partially open option is valid for both electronic and mechanical
limit switches, provided that for the latter, the partial opening cam is connected
to input "1/2 UP".
At the end of the procedure, switch the contact connected to the input to
activate partial opening.
When an open command is given, the door will stop at the limit set in parameter
P12.