5. LIST OF PARAMETERS AND ERRORS
Parameter No.
Parameter name
Unit
Minimum
value
Maximum
value
Default value
STD
Default value
EE_1
Default value
EE_2/EE_3
MLS
ELS
From version
0
Set door positions
Button = Upper limit stop
Button = Lower limit stop
Both buttons =Partial opening limit stop
Num. - - - - - - x 0.33
Maintenance
1 Cycle counter (1 increment = 10 door cycles) Num. 0 9999 0 0 0 x x 0.33
2 Cycles limit for door maintenance Num. 0 9999 2000 3500 3500 x x 0.33
3 Restart counter Num. 0 65535 0 0 0 x x 0.33
4 Automatic door cycles (waiting time between manoeuvres) Sec 0 255 0 0 0 x x 0.33
5
Door status display options
0 = Basic display (with dashes)
1 = Display with dashes during movement and with letters on reaching
limit stops
2 = Display all with letters
Num. 0 2 0 0 0 x x 0.40
6 Storage of last 10 errors - - - - - - x x 0.46
Electronic encoder
10 Upper limit stop Incr. 0 8191 Off Off Off - x 0.33
11 Lower limit stop Incr. 0 8191 Off Off Off - x 0.33
12 Half-open limit switch (partial opening if set) Incr. 0 8191 Off Off Off - x 0.33
13 Pre-limit distance (in relation to lower limit stop) Incr. 1 700 50 50 50 - x 0.33
14 Safety limit stop distance Incr. 0 5000 100 250 250 - x 0.33
15 Nice encoder rmware version Num. 0 - - - - - x 0.33
16 Number of operating hours run by Nice encoder Hours 0 9999 - - - - x 0.33
17
Minimum distance for photocell trigger
(see also parameter P104)
Incr. 0 8191 Off Off Off - x 0.57
Overrun control
20 Adjustment of maximum overrun correction Incr. 0 240 2 2 2 - x 0.33
21
Maximum overrun correction for upper limit stop
(can only be set if P20 = 0)
Incr. 0 200 50 70 70 - x 0.33
22
Maximum overrun correction for lower limit stop
(can only be set if P20 = 0)
Incr. 0 200 50 70 70 - x 0.33
23 Initial overrun at upper limit stop Incr. ro - - - - - x 0.33
24 Initial overrun at lower limit stop Incr. ro - - - - - x 0.33
Adjustment of automatic ground adaptation
30
Automatic ground adaptation options:
0 = No automatic ground adaptation
1 = Limited to lower limit stop
2 = Including downward correction
Num. 0 2 0 0 0 - x 0.33
31 Maximum encoder increments for ground search Incr 0 240 5 5 5 - x 0.33
32
Maximum limit for ground adaptation beyond lower limit stop
(default maximum limit P11 - 50)
Incr. 0 8191
P11-
50
P11-
50
P11-
50
- x 0.33
33 Minimum height (in percent) to validate ground adaptation % 0 100 30 30 30 - x 0.33
Automatic closing / Air curtain
40
Automatic closing options
0 = Standard automatic closing
1 = Automatic closing is not disabled by pressing the STOP button
2 = All commands ignored during waiting time
3 = Automatic closing activates regardless of door position
Num. 0 3 0 0 0
x
x
x
x
x
x
0.33
0.45
1.44
41
Waiting time for automatic closing
0 = Automatic closing deactivated
Sec 0 9999 0 0 0 x x 0.33
42 Trafc light warning time
1/10
Sec
0 240 0 0 0 x x 0.33
43
Waiting time for automatic closing if photocells are activated
0 = Disabled
Sec 0 240 0 0 0 x x 0.33
44
Disabling of automatic closing after n attempts to trigger safety edge
0 = Not disabled
1 = Disabled after 1 attempt
2-5 = Disabled after n attempts
Num. 0 5 3 3 3
x
x
x
x
x
x
0.33
1.33
0.33
45 Time delay for air curtain deactivation Sec 0 9999 0 0 0 x x 1.05
5.1 Service parameter table - “P” series