EN
English – 29
F34
Error in photocell test (only for D-Pro Automatic R10)
Press the STOP button on the front panel to attempt a new photocell test.
The control unit automatically clears the error as soon as the test is successful
F35
The difference between the upper and lower limit
switch is less than 500 or greater than 8100 encoder
increments
Contact a technician for encoder replacement
F60
Communication error with inverter (inverter error not
read correctly)
Press the STOP button on the front panel.
If the error persists, switch off the control unit and wait approximately one minute before switching it back on
F61
Communication error with inverter (inverter error
reading not possible)
Press the STOP button on the front panel.
If the error persists, switch off the control unit and wait approximately one minute before switching it back on
F100
Release cable input activation (Terminal X2-J10)
These errors clear automatically as soon as the control unit detects the safety chain is closed
again
F101
Key release activation (Terminal X9-J14)
F102
Emergency button activation ("Notaus” terminal)
F103
Absence of boost capacitor control board (Terminal
X8)
F104
Motor thermal relay activation or manual release
activation
5.5 Nice inverter errors list
TABLE 19 B - Nice inverter errors list
Error Description Solution
F200
Short-circuit protection.
The error will rst appear as “E200” and then change
to “F200” when it can be cleared
Press the STOP button on the front panel
F201
Overvoltage protection Press the STOP button on the front panel
F202
Undervoltage protection Press the STOP button on the front panel
F203
Over- or under-temperature protection Press the STOP button on the front panel
F204
IGBT module overload protection (motor control)
The error will rst appear as “E204” and then change
to “F204” when it can be cleared
Press the STOP button on the front panel
F205
Motor overload protection (current too high on
phases: see parameter U24)
The error will rst appear as “E205” and then change
to “F205” when it can be cleared
Press the STOP button on the front panel
F206
Error history (if U5 value > 29)
Reset U5 value by entering the parameter and holding down the STOP button on the front
panel until the value returns to 0
F207
Software overcurrent protection Press the STOP button on the front panel
F208
Protection from broken cables (missing motor
phase)
Check the motor is correctly connected and/or a phase cable is not broken
The control unit automatically clears the error as soon as the resistor is reconnected
F209
Protection for communication failure with D-Pro
Automatic
Reboot the control unit
F210
Protection for communication failure with encoder Reboot the control unit
F211
Short-circuit protection on IGBT module Press the STOP button on the front panel
F212
IGBT module integrity protection Press the STOP button on the front panel
F213
Braking resistor broken or not connected Contact a technician