Table 3‐4 Common Operating Parameters
Parameter Parameter Name Purpose Default Value
4
Ready Delay Time
A timer that delays the activation of the ready
LED for a pre‐defined time period after the tank,
hoses, and guns are at the desired set‐point
temperature. The ready delay timer will only
activate if the temperature of the tank, at the
time the melter is turned on, is below its
assigned set‐point temperature by
27 C (50 F) or more.
0 minutes
5
Service Interval Time
A timer that turns on a service LED when the
value set for the timer equals the number of
hours that the heaters have been on. The
service LED is used to signal the need for
maintenance.
500 hours
8
Automatic Pump On
Determines whether the pump will turn on
automatically when the all components are at
their desired set‐point temperature (enabled) or
whether the pump must be turned on manually
(disabled).
Enabled
11
Create Password
Sets a password that must be entered before
any melter operating parameter or set‐point
temperature can be changed.
5000
20
Temperature Units
Sets the units of the temperature display to
degrees Celsius (C) or to degrees Fahrenheit
(F).
C
21
Over Temperature
Delta
Sets the number of degrees that any heated
component can exceed its assigned set‐point
temperature before an over temperature fault
occurs.
15 C (25 F)
22
Under Temperature
Delta
Sets the number of degrees that any heated
component can drop below its assigned
set‐point temperature before an under
temperature fault occurs.
25 C (50 F)
23
Standby Delta
Sets the number of degrees that the
temperature of all heated components will be
decreased when the melter is placed into the
standby mode.
50 C (100F)
26
Manual Standby
Time
Sets the amount of time the melter will remain in
the standby mode after the standby key is
pressed.
Disabled
50 to 77
Seven‐day Clock
A group of parameters that control the melter's
clock. The clock is used to automatically turn
the
heaters on and off and to place the melter into
the standby mode.
Disabled