System Faults
7
7.10 Incorrect Sampling Period with UC SII CPU
Message displayed at initialisation
WARNING: SAMPLING PERIOD
IS NOT A MULTIPLE OF 2 ms
CONTINUE (Y/N)?
Comment
The sampling period set by parameter P50 (See Parameter Manual) is not suitable for operation with a UC SII CPU
(the value must be a multiple of 2 ms).
Actions
Acknowledge the message. ☞
Y
The system is available. The sampling period is rounded down to the next lower multiple of 2 ms, but parameter P50
is not modified.
Enter a correct sampling period in parameter P50 (See Parameter Manual).
Reset the system to take the new parameter into account.
This action can be carried out later if the system operates correctly with the rounded-down value of the sampling period.
7.11 Sensor Declared Connected Several Times to the QVN Card
Message displayed at initialisation
ERROR: SENSOR DECLARED CONNECTED SEVERAL
TIMES TO THE QVN CARD
CONTINUE (Y/N)?
Comment
A QVN sensor is declared connected several times in parameter P70 (See Parameter Manual).
Actions
Acknowledge the message. ☞
Y
The system is available, but the machining modes are inhibited and power cannot be applied to the system.
The "PRSOV" system fault indicator is displayed in the status window (See 3.1.3).
Enter correct sensor addresses in parameter P70 (See Parameter Manual).
Reset the system to take the new parameter into account.