System Wiring iTrans Fixed Point Single/Dual Gas Monitor
4-8 iTrans User Manual (P/N: 77023554-1)
NOTE: If using remote sensors and the does not recognize the sensor
upon power up (displays a sensor fault), check the placement of this jumper. If the
jumper is on terminals 1-2, move the jumper to terminals 2-3.
For digital ModBus signal and power use a minimum of 4 conductors #18 AWG
insulated and shielded cable.
Shielding from either the controller or remote sensors should be bonded to the
enclosure screw located inside the .
Figure 4-6. Wiring Diagram for Dual On-board Sensors