Clock timer
Mode: Heat
Period: 00:00~00:00
T water tank: 50°C
4.11.
After accessing the “Clock timer” function, you will be
able to set all the parameters needed for a timed start
of the unit:
t “Clock timer” = enable or disable the timer
t “Mode“ = select the mode to be used during the time
band (each click changes the mode)
t “Period“ = access this page to set the start and
end time for the time band
t “T-tank ctrl.“ = set (if the mode so envisages) the
set for the domestic hot water production stor-
age tank
t “WOT-heat“ = set the value (if envisaged) for the
water production set-point (terminal system
side)
Click on the “Period” label to open the page with the
timer start and end time labels; set by rst of all click-
ing on the label of the time you want to set, then slid-
ing your ngertip over the time values until you select
those required. Lastly, press the top right button to
save the data entered.
Click on the labels for parameters with numeric values
to be inserted to display a numeric keypad (with an
indication of the range of permitted values) which you
can use to enter the required values.
00 00
01 01
02 02
23 59
22 58
Clock timer
Start timer: 00:00
End timer: 00:00
00 00
01 01
02 02
23 59
22 58
Timer
Timer: O
Modalità: Riscaldamento
Periodo: 00:00~00:00
T Serbatoio ACS: 50°C
T Mandata Ra: 45°C
Min: 20 Max: 60
X
0
1 2 3
4 5 6
7 8
0 -
9
OK
00 00
01 01
02 02
23 59
22 58
Clock timer
Mode: Heat
Period: 00:00~00:00
T water tank: 50°C
NOTES:
1. If the requested mode is “Hot water”, the “WOT-Cool” or “WOT-heat“ parameter will not be displayed.
2. Every time you press on the label, the value will change. Once you have selected the required value,
press the icon to save and implement the setting.
3. If the water tank for this model is not installed (and correctly set), the references to hot water
production will not be available.
4. If the weekly timer and the standard timer are set at the same time, the weekly timer takes priority.
5. The timer start must always be prior to the timer end, otherwise the period will not be valid.
6. The timer for hot water production will only be available if the operating mode envisages hot water
17
production.
7. The timer function will only work once. If you want to use it again, you must re-set it.
8. The timer is deactivated if the unit is manually switched on before the timer start time.
9. If the relative function is activated (paragraph 8.3), the value of this parameter will be stored in the
memory and automatically reset after any possible voltage failure.
10. The default value for this function is “Off”.
After accessing the “Temp. timer” function, you can
set programmed variations of the water delivery set-
point (this set-point will depend on the currently ac-
tive operating mode). The function can be activated
or deactivated by clicking on the “Temp. timer” label;
click on the “Period 1” label to specify the time at
which the water delivery set-point is to be changed,
setting it to the value specified in the “WOT-heat 1”
parameter (which when clicked will display a numeric
keypad to change its value). Set “Period 2” with related
“WOT-heat 2” in the same way.
Click on the labels for the delivery temperature pa-
rameters to display a numeric keypad (with an indica-
tion of the range of permitted values) which you can
use to enter the required values.
00 00
01 01
02 02
23 59
22 58
Temp. timer
m timr: Off
Period 1: 00:00
WT heat 1: 45°C
Period 2: 00:00
WT heat 2: 45°C
NOTES:
1. Press the icon to save and implement the setting.
2. This function is not available if DHW mode is set.
3. To activate this function, the unit must be enabled.
4. The time bands apply to the current day only.
5. If “Weekly timer”, “Preset mode“, “Clock timer”, “Temp. timer“ are set at the same time, priority is given
to the last one of these to be set.
00 00
01 01
02 02
23 59
22 58
Fasce Orarie
ac Orari: Off
Periodo 1: 00:00
T Mandata Risc 1: 45°C
Periodo 2: 00:00
T Mandata Risc 2: 45°C
Min: 25 Max: 60
X
0
1 2 3
4 5 6
7 8
0 -
9
OK
00 00
01 01
02 02
23 59
22 58
Temp. timer
m timr: Off
Period 1: 00:00
WT heat 1: 45°C
Period 2: 00:00
WT heat 2: 45°C
4.12. Setting programmed setting changes on system water delivery (Temp. timer)