CP TD1 Reference Manual V 1.44
72
like the bushings and the transformer tank (flashovers) with the
unscreened part of the high-voltage test cable must be avoided.
Connect the IN A, e.g. to the low-voltage winding, IN B, e.g. to the tertiary
winding (according to the connection instructions).
Short circuit all bushing CTs.
Do not make high-voltage tests on transformers under vacuum.
The test voltage should be chosen with respect to the rated voltage of the
winding.
All tests should be made with oil temperatures near 20°C. Temperature
corrections can be calculated by using correction curves, but they depend
a great deal on the insulation material, the water content and many other
parameters. This way the correction has limited accuracy.
6.2.1 Three-Winding Transformer
A transformer contains a complicated insulation system. High- and low-voltage
windings have to be insulated to the tank and the core (ground) and against each
other. All these insulation gaps should be checked regularly. Normally in a two-
winding power transformer, C-Tan-Delta measurements are made for all
insulation gaps: HV to LV, HV to ground, LV to ground.

Table of Contents

Other manuals for Omicron CP TD1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omicron CP TD1 and is the answer not in the manual?

Omicron CP TD1 Specifications

General IconGeneral
BrandOmicron
ModelCP TD1
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals