Capacitance and Dissipation Factor Measurement
39
5 Capacitance and Dissipation Factor
Measurement
Capacitance (C) and Dissipation Factor (DF) measurement is an established
and important insulation diagnosis method. It can detect:
Insulation failures
Aging of insulation
Contamination of insulation liquids with particles
Water in solid and liquid insulation
Partial discharges
5.1 Theory
In an ideal capacitor without any dielectric losses, the insulation current is
exactly 90° leading according to the applied voltage. For a real insulation with
dielectric losses this angle is less than 90°. The angle
δ = 90° - ϕ is called loss
angle. In a simplified diagram of the insulation, C
p
represents the loss-free