Technical Data
123
11.2 Environmental Conditions
Table 11-1 Climate
Characteristic Rating
Temperature Operating –10…+55 ºC (+14…+131 ºF)
Storage and
transportation
–20…+70 ºC (–4…+158 ºF)
Max. altitude 2000 m
Relative humidity 5…95%; no condensation
Tested according to IEC 60068-2-
78
Table 11-2 Shock, Vibration, Noise Immunity
Characteristic Rating
Shock IEC 60068-2-27 (operating), 15 g/11 ms, half-
sinusoid
Vibration IEC 60068-2-6 (operating), 10 to 150 Hz,
acceleration 2 g continuous (20 m/s
2
); 10 cycles
per axis
Noise Immunity Electrostatic: 15 mA induced noise into any test
lead without losing measurement accuracy at
maximum interference to specimen current of
20:1
Electromagnetic: 500 µT, at 60 Hz in any
direction