EasyManuals Logo

Omicron CP TD1 Reference Manual

Omicron CP TD1
188 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #70 background imageLoading...
Page #70 background image
CP TD1 Reference Manual V 1.44
70
In addition to the previous table , it should be taken into account that overheating
is often caused by bad contacts in the tap selector. In order to find out the reason
for high gas values, further tests have to be performed on the transformer.
Common test methods are:
Winding resistance measurement
On-Load Tap Changer (OLTC) test
Turns ratio measurement
Excitation current measurement
Measurement of leakage reactance
Capacitance and Dissipation factor measurement
All the mentioned tests can be done with the CPC 100 + CP TD1. This
instrument is the ideal test and analysis instrument for transformer diagnosis
with these measuring possibilities.
6.2 Capacitance and DF Measurement of Transformer
Windings
General
The transformer must be taken out of service and completely isolated
from the power system.
The proper grounding of the transformer tank has to be checked.
The bushing high-voltage terminals must be isolated from the connection
lines.
All bushing terminals of one winding group, which means A, B, C (and
Neutral) of high-voltage winding, A, B, C (and Neutral) of low-voltage

Table of Contents

Other manuals for Omicron CP TD1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omicron CP TD1 and is the answer not in the manual?

Omicron CP TD1 Specifications

General IconGeneral
BrandOmicron
ModelCP TD1
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals