OMICRON 25
Application
3 Application
3.1 Preparations on site
DANGER
Death or severe injury caused by high voltage or current
Prior to connecting a test object to the CP TD12/15, the following steps need to be
carried out by an authorized and qualified employee of the utility:
Turn off and disconnect the high voltage from the test object.
Protect yourself and your working environment against an accidental re-connection of
high voltage by other persons and circumstances.
Verify a safe isolation of the test object.
Ground and short-circuit the test object’s terminals using a grounding set.
Protect yourself and your working environment with a suitable protection against other
(possibly live) circuits.
Protect others from accessing the dangerous area and accidentally touching live parts
by setting up a suitable barrier and, if applicable, warning lights.
If there is a longer distance between the location of the CP TD12/15 and the area of
danger (that is, the test object), a second person with an additional "Emergency Stop"
button is required.
DANGER
Death or severe injury caused by high voltage or current
If you have a cardiac pacemaker, do not use the CP TD12/15! If you have another type
of electronic medical implant consult your doctor before operating the CP TD12/15.
Before operating the CP TD12/15, make sure there is no person with an electronic
medical implant in the immediate vicinity.