Power sup-
ply line
Standard
applicable
motor (kW)
Inverter model
Specifica-
tions
Molded
case circuit
breaker
(MCCB)
*1
Earth leakage circuit breaker (RCD/
ELCB)
*1
Rated cur-
rent
Rated cur-
rent
Sensitivity
current
*2
Max. fault
loop impe-
dance
With
DC
re-
ac-
tor
With
out
DC
re-
ac-
tor
With
DC
re-
ac-
tor
With
out
DC
re-
ac-
tor
Three-
phase 200
V
0.1 3G3M1-A2001-
ECT
HHD 5 5 5 5 30 mA 200 Ω
0.2 HND
3G3M1-A2002-
ECT
HHD
0.4 HND
3G3M1-A2004-
ECT
HHD
0.75 HND 10 10
3G3M1-A2007-
ECT
HHD
1.1 HND 10 10
1.5 3G3M1-A2015-
ECT
HHD 15 15
2.2 HND 20 20
3G3M1-A2022-
ECT
HHD
3 HND 20 30 20 30
3.7 3G3M1-A2037-
ECT
HHD
5.5 HND 30 40 30 40
3G3M1-A2055-
ECT
HHD 50 50
7.5 HND 40 75 40 75
3G3M1-A2075-
ECT
HHD
11 HND 50 100 50 100
3G3M1-A2110-ECT HHD
15 HND 75 125 75 125
3G3M1-A2150-
ECT
HHD
18.5 HND 100 150 100 150
3G3M1-A2185-
ECT
HHD
22 HND 175 175
*1. The frame size and model of MCCB, RCD or ELCB (with overcurrent protection function) change according to the ca-
pacity of the power transformer
. For details on selection method, refer to related technical data.
*2.
The sensitivity current setting of the TT system differs according to each country. Follow the instructions of the relevant
authority.
2 Design
2-74
M1 Series EtherCAT Type User’s Manual (I670)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron 3G3M1-A4004-ECT and is the answer not in the manual?

Omron 3G3M1-A4004-ECT Specifications

General IconGeneral
BrandOmron
Model3G3M1-A4004-ECT
CategoryInverter
LanguageEnglish

Related product manuals