Main Circuit Terminal Block Screw Sizes, Tightening Torque and
W
ire Sizes
Power supply
system
Standard applicable
motor (kW)
Inverter Model
HHD/HD/HND/ND
modes
Tightening torque
lb-in (Nm)
Wire size AWG (mm
2
)
Main Terminal
Inverter's
grounding
Control circuit
auxiliary input
Main circuit copper wire
G
Control circuit
auxiliary input
L1/R, L2/S, L3/T U, V, W
60°C Cu Wire
75°C Cu Wire
Remarks
60°C Cu Wire
75°C Cu Wire
Remarks
Inverter's
grounding
Thre
e-
phas
e
200
V
0.1 3G3M1-
A2001-
ECT
HHD 10.6
(1.2)
15.9
(1.8)
- 14
(2.1)
14
(2.1)
*3
14
(2.1)
14
(2.1)
*3
14
(2.1)
-
0.2 3G3M1-
A2001-
ECT
HND
3G3M1-
A2002-
ECT
HHD
0.4 3G3M1-
A2002-
ECT
HND
3G3M1-
A2004-
ECT
HHD
0.75 3G3M1-
A2004-
ECT
HND
3G3M1-
A2007-
ECT
HHD
1.1 3G3M1-
A2007-
ECT
HND
1.5 3G3M1-
A2015-
ECT
HHD
2.2 3G3M1-
A2015-
ECT
HND 12
(3.3)
3G3M1-
A2022-
ECT
HHD
3 3G3M1-
A2022-
ECT
HND
2 Design
2-85