Loading...
Power supply
system
Standard applicable
motor (kW)
Inverter Model
HHD/HD/HND/ND
modes
Tightening torque
lb-in (Nm)
Wire size AWG (mm
2
)
Main Terminal
Inverter's
grounding
Control circuit
auxiliary input
Main circuit copper wire
G
Control circuit
auxiliary input
L1/R, L2/S, L3/T U, V, W
60°C Cu Wire
75°C Cu Wire
Remarks
60°C Cu Wire
75°C Cu Wire
Remarks
Inverter's
grounding
Sin-
gle-
phas
e
200
V
1.5 3G3M1-
AB015-
ECT
HHD 10.6
(1.2)
15.9
(1.8)
- 12
(3.3)
12
(3.3)
*3
14
(2.1)
14
(2.1)
*3
10
(5.3)
-
2.2 3G3M1-
AB015-
ECT
HND 10
(5.3)
10
(5.3)
3G3M1-
AB022-
ECT
HHD
3 3G3M1-
AB022-
ECT
HND
3.7 3G3M1-
AB037-
ECT
HHD 27
(3)
27
(3)
6
(13.3
)
8
(8.4)
12
(3.3)
12
(3.3)
8
(8.4)
*1. Wires can be connected without any terminal treatment.
*2. Only 75°C (167°F) Cu wiring can be used.
*3. Shows common wiring sizes for UL Open Type and Enclosed Type. Please contact us separately if dedicat-
ed UL Open T
ype wiring sizes are required.