Parameter No. Item Range Display item
3010Hex-48Hex
Main circuit DC voltage
Monitor
0.0 to 999.0 [V]
Although the Main Circuit DC Voltage of
the inverter is displayed in increments
of 0.1 V, the data changes in incre-
ments of 1 V
.
3010Hex-49Hex
Internal Air Highest Tem-
perature
20 to 125 [°C]
The maximum value of the internal air
temperature for each hour is displayed
in increments of 1 degree.
Display unit: °C (for 20°C and below,
20°C is displayed.)
Since there is no internal air tempera-
ture sensor in 15 kW and lower models,
3010Hex-49Hex displays 0.
3010Hex-4AHex
Heat Sink Maximum T
em-
perature
20 to 125 [°C]
The maximum value of the cooling fin
temperature for each hour is displayed.
Display unit: °C (for 20℃ and below,
20
℃ is displayed.)
3010Hex-4BHex
Maximum Effective Current
Value
0.00 to 999.9 [A]
The maximum ef
fective current value
for each hour is displayed.
3010Hex-4CHex
Main Circuit Capacitor's
Capacitor Monitor
0.0 to 100.0 [%]
The factory default value of the current
main circuit capacitor's capacitor is dis-
played as 100.0%.
3010Hex-44Hex
Cumulative Run Time of
Capacitors on Printed Cir-
cuit Boards
0 to 9999 [x10h]
The time obtained by multiplying the co-
efficient based on the ambient tempera-
ture conditions with the cumulative time
during which voltage is applied to the
electrolytic capacitors on printed circuit
boards is displayed as the cumulative
operation time.
Measurement range: 0 to 99990 hours
If 99990 hours is exceeded, the accu-
mulation operation stops.
For details, refer to
8-8-10 Capacitor
Life Warning Signal (WAC) on page
8-85.
3010Hex-45Hex
Cumulative Run Time of
Cooling Fan
0 to 9999 [x10h]
The cumulative time when the cooling
fan was operating is displayed.
Counting is not performed when the
Cooling Fan Function Selection (Object
3008Hex-07Hex) is enabled and the
cooling fan has stopped.
Measurement range: 0 to 99990 hours
If 99990 hours is exceeded, the accu-
mulation operation stops.
3010Hex-4FHex Number of Startups 0 to 65530
The number of operations of the 1st
motor (number of times the RUN com-
mand for the inverter is turned ON) is
calculated and displayed. If 65530 oper-
ations is exceeded, the value returns to
0 and the calculation continues.
8 Other Functions
8-12
M1 Series EtherCAT Type User’s Manual (I670)