Parameter No. Item Range Display item
3010Hex-52Hex Integrated Power Monitor
0.000 to 9999
[100kWh]
The integrating electric power con-
sumption is displayed. 0.1 kWh to
999,900 kWh is displayed for 0.001 to
9999, with 1 = 100 kWh. The value re-
turns to 0 at 1,000,000 kWh.
The integrated electric power consump-
tion and the integrated electric power
data can be reset by setting Display Co-
efficient for Integrated Power
(3005Hex-34Hex) to “0.000.” If 999,900
kWh is exceeded, the value returns to
0. Integration is not performed when
0.000 is still set.
3010Hex-53Hex
Data Used Integrating
Electric Power
0.001 to 9999
The integrated electric power consump-
tion (1.000 = 100 kWh) × Display Coef-
ficient for Integrated Power
(3005Hex-34Hex) is displayed as the
integrated electric power data.
The setting range of Display Coefficient
for Integrated Power (3005Hex-34Hex)
is 0.000 to 9999.
Display unit: None
If 9999 is exceeded, the accumulation
operation stops.
The decimal point position moves de-
pending on the size of the integrated
electric power data, and the display res-
olution changes. The integrated electric
power data can be reset by setting
3005Hex-34Hex to “0.000.” Integration
is not performed when 0.000 is still set.
3010Hex-58Hex
Inverter ROM V
ersion 1
Main
0 to 59999
The version of the inverter ROM1 is dis-
played.
3010Hex-59Hex
Inverter ROM Version 2
Sub
0 to 59999
The version of the inverter ROM2 is dis-
played.
3012Hex-29Hex 1st Cumulative Run Time 0 to 9999 [x10h]
The cumulative time of the 1st motor
run time is displayed.
Measurement range: 0 to 99990 hours
If 99990 hours is exceeded, the value
returns to 0 and the calculation contin-
ues.
3003Hex-3EHex
Inverter Internal Air Tem-
perature Monitor (Real-
time value)
20.0 to 125.0 [°C]
The current internal temperature of the
inverter is displayed. Although the dis-
play is in increments of 0.1°C, the data
changes in increments of 1°C.
Display unit: °C
Since there is no internal air tempera-
ture sensor in 15 kW and lower models,
“--------” is displayed. 0 is displayed in
3003Hex-3EHex.
8 Other Functions
8-13
M1 Series EtherCAT Type User’s Manual (I670)
8-1 Status Monitors
8
8-1-3 Maintenance Information