De-
tec-
tion
tar-
get
Detection method
Individual
output ter-
minal
*1
Monitor No. Remarks
Main
cir-
cuit
ca-
paci-
tor
Measure the discharge time of
the main circuit capacitor when
the main power supply is shut of
f
and calculate the capacity of the
main circuit capacitor
.
It is judged that the end of life
has been reached when capacity
has reached 85% of the factory
default capacitor capacity or the
main circuit capacitor capacity
(pre-measured at startup) in a
user normal operation state.
WAC termi-
nal
(240: W
AC)
Main Circuit Ca-
pacitor's Capacitor
Monitor
(3010Hex-4CHex)
Adjustment is possible
(For details, refer to
8-8-10 Ca-
pacitor Life W
arning Signal
(W
AC) on page 8-85.)
Can be disabled by Protection/
Maintenance Function Mode Se-
lection (3008Hex-63Hex).
The time during which voltage is
applied to the main circuit capac-
itor (the time during which the
main power supply is ON) is
counted. Also, the time is cor-
rected by measuring the capacity
of the main circuit capacitor.
When the operation time ex-
ceeds 87,000 hours (10 years)
*2
,
it is judged that the end of life
has reached.
Elapsed time
Service Life of
Main Circuit Ca-
pacitor Elapsed
T
ime
(3003Hex-4DHe
x)
Remaining time
Service Life of
Main Circuit Ca-
pacitor Remain-
ing T
ime
(3003Hex-4EHe
x)
Can be reset by Service Life of
Main Circuit Capacitor Remain-
ing Time (3008Hex-4EHex).
Elect
rolyt-
ic
ca-
paci-
tor
The time during which voltage is
applied to the electrolytic capaci-
tor is counted. Also, the elapsed
time is corrected by the ambient
temperature.
When the operation time ex-
ceeds 87,000 hours (10 years), it
is judged that the end of life has
reached.
-
Cumulative Run
Time of Capacitors
on Printed Circuit
Boards
(3010Hex-44Hex)
Can be reset by Cumulative Run
Time of Electrolytic capacitor
(3008Hex-31Hex).
Cool
ing
fan
The time during which the cool-
ing fan is operating is counted.
When the operation time ex-
ceeds 87,000 hours (10 years), it
is judged that the end of life has
reached.
W
AF termi-
nal
(241: WAF)
Cumulative Run
Time of Cooling
Fan
(3010Hex-45Hex)
Can be reset by Cumulative Run
Time of Cooling Fan
(3008Hex-2CHex).
*1. Select by output terminal function selection.
*2. With specifications and models shown below, the life is 61,000 hours (7 years) according to Load Mode Se-
lection (3004Hex-51Hex).
HND mode: A2022/037, A4022/040, AB002-022
ND mode: All models
8 Other Functions
8-89
M1 Series EtherCAT Type User’s Manual (I670)
8-8 Functions Related to Protection, Warning and Various Output Signals
8
8-8-14 Life Alarm (LIFE)